When Is Backflow Testing Required?
The exact wording varies, but BC programs repeatedly use the same core testing triggers. A testable assembly is commonly tested upon installation, once every year, after internal cleaning or repair, after replacement or relocation, after alterations that may affect the assembly, and whenever the authority requires a test because of a complaint, incident, survey, or concern.
1. Upon Installation
A new assembly should be tested after installation and before it is relied upon as functioning protection. New piping can contain debris, solder, scale, thread sealant, or construction material that prevents a check valve from sealing. The installation test also confirms the correct device information and creates the initial record for the local program.
2. Annually After Installation
Annual testing verifies that springs, seals, discs, check valves, relief valves, air-inlet components, and shutoff valves continue to perform within the required criteria. Water can continue flowing through an assembly even when its internal protection has failed, so appearance and normal water service do not prove that the device will prevent backflow.
3. After Repair, Cleaning, or Overhaul
Opening the assembly changes the condition that was tested. After parts are cleaned, replaced, or adjusted, the assembly is normally retested to confirm the completed repair produced a passing result. A repair invoice alone is not a substitute for a passing field test where testing is required.
4. After Replacement or Relocation
Replacement introduces a new assembly, serial number, model, and installation condition. Relocation changes piping and hydraulic conditions. The local record must often be updated, and the new or relocated assembly must be tested before the work is considered complete.
5. After Piping Alterations
Changes upstream or downstream can affect shutoff-valve integrity, orientation, pressure, drainage, accessibility, or the hazard being protected. Local requirements may call for testing after alterations to the device or the piping that supplies it.
6. At the Authority's Request
A water supplier may require an additional test following a suspected backflow incident, complaint, change of use, cross connection survey, missed deadline, emergency, or reason to believe the assembly may not be working properly.